Pre-Insulated Pipe Shoe LK-HV

Application

Pipe Shoe with insulation
With PUR insulation insert for pipes on suitable surfaces. Height-adjustable in steps of 2.5 mm. When resting on steel beams, a minimum flange width of 80 mm is recommended.

Scope of delivery

Upper and lower part are bolted together allowing height adjustment. The slide plate is fixed to the lower part. Pipe Clamp, load spread metal sheet and insulation insert are pre-assembled.

Description

Technical Data

NB Form Height H
as delivered [mm]
Height H
range [mm]
DN 25 – 50 Single clamp 150 137.5 … 167.5
DN 65 – 80 Single clamp 150 147.5 … 177.5
DN 100 – 250 Double clamp 150 150 … 180
DN 300 Double clamp 150 150 … 160

Tightening torque screw connections:

Clamping bolts tightening torque
[Nm]
height adjustment tightening torque
[Nm]
DN 25 – 80 50 bolts in the bar 80
DN 100 – 300 60 bolts in the bar 80

Insulation thickness:

NB insulation thickness
[mm]
DN 25 – 50 50
DN 65 – 250 60
DN 300 80

The laying rules of DIN 4140 have to be respected (existing gaps have to be sealed by means of sealing paste if necessary).

Dimensions:
Metal plate: L = 250 mm x B = 100 mm
Slide plate incl.: L = 256 mm x B = 105 mm
Material:
Metal parts: Steel, HCP
Grub screws, nuts: Steel, HCP
Slide plate: Polyamide 6.0, glass fibre reinforced, black
Insulation insert: PUR, 200 kg/m 3
Load spread sheet Aluminium (on request: Steel, galvanised, stainless steel)
Temperature range: -30 up to +120° C

Approvals / Compliance

Type D (pipe)
[mm]
W
[kg]
Quantity
[pack]
Part
number
LK – HV 150 DN 25 33.7 4.1 1 110110
LK – HV 150 DN 32 42.4 4.2 1 110111
LK – HV 150 DN 40 48.3 4.3 1 110112
LK – HV 150 DN 50 60.3 4.4 1 110113
LK – HV 150 DN 65 76.1 6.2 1 110114
LK – HV 150 DN 80 88.9 6.6 1 110115
LK – HV 150 DN 100 114.3 12.0 1 110116
LK – HV 150 DN 125 139.7 13.9 1 110117
LK – HV 150 DN 150 168.3 14.5 1 110118
LK – HV 150 DN 200 219.1 16.6 1 110119
LK – HV 150 DN 250 273.0 18.6 1 110120
LK – HV 150 DN 300 323.9 24.2 1 110121